Unscreened XHHW-2 Cable with Ground Wire
Applications
These cables are use in class 1, Division 2 Hazardous locations, may be installed in trays, wire ways,
ducts, conduit and aerially when properly supported by a messenger. They are approved for direct
burial, wet or dry locations and outdoors in cable trays where a sunlight resistant rating is required.
Standards
ICEA S-73-532; ICEA S-95-658; UL 1277; UL 44
Construction
Conductor: Bare, annealed copper conforming to ASTM B3 and B8
Ground wires: Sized as required by UL 1277. Sizes 14 AWG to 6 AWG have an insulated green ground
wire. Sizes 4 AWG and larger have a bare ground wire.
Insulation: Flame-retardant XLPE meeting the requirements for XHHW-2 per UL 44 and the
requirements of ICEA S-95-658 for XLPE insulation as standard. Sizes 14 AWG to 8 AWG are VW-1,
and sizes #6 AWG and larger are non-VW-1.
Binder tape
Jacket: Special PVC, flame retardant, UL listed sunlight and moisture resistant, meeting the
requirements of UL 1277. Color: Black
Chemical resistance: Aliphatic and aromatic hydrocarbon resistance
3 Cores, 600V,Rated 90°C
Conductor Size |
Ground Wire Size |
Insulation Thickness |
Jacket Thickness |
Nom. O.D. |
Approx Weight |
Ampacity |
(AWG/kcmil) |
(AWG) |
(mm) |
(mm) |
(mm) |
(kg/km) |
(amps) |
12 |
12 |
0.76 |
1.14 |
11.82 |
216 |
30 |
10 |
10 |
0.76 |
1.14 |
13.30 |
305 |
45 |
8 |
10 |
1.14 |
1.52 |
16.89 |
480 |
55 |
6 |
8 |
1.14 |
1.52 |
19.53 |
672 |
75 |
4 |
8 |
1.14 |
1.52 |
20.78 |
886 |
95 |
3 |
6 |
1.14 |
2.03 |
23.28 |
1226 |
110 |
2 |
6 |
1.14 |
2.03 |
25.12 |
1372 |
130 |
1 |
6 |
1.40 |
2.03 |
27.75 |
1786 |
150 |
1/0 |
6 |
1.40 |
2.03 |
30.00 |
2021 |
170 |
2/0 |
6 |
1.40 |
2.03 |
32.33 |
2474 |
195 |
3/0 |
4 |
1.40 |
2.03 |
35.59 |
3209 |
225 |
4/0 |
4 |
1.40 |
2.03 |
39.13 |
3729 |
260 |
250 |
4 |
1.65 |
2.03 |
41.51 |
4376 |
290 |
300 |
3 |
1.65 |
2.79 |
45.72 |
5050 |
320 |
350 |
3 |
1.65 |
2.79 |
49.12 |
6105 |
350 |
400 |
3 |
1.65 |
2.79 |
51.33 |
7169 |
380 |
500 |
2 |
1.65 |
2.79 |
55.63 |
8438 |
430 |
4 Cores, 600V, Rated 90°C
Conductor Size |
Ground Wire Size |
Insulation Thickness |
Jacket Thickness |
Nom. O.D. |
Approx Weight |
Ampacity |
(AWG/kcmil) |
(AWG) |
(mm) |
(mm) |
(mm) |
(kg/km) |
(amps) |
10 |
10 |
0.76 |
1.52 |
15.33 |
401 |
40 |
8 |
10 |
1.14 |
1.52 |
18.65 |
582 |
55 |
6 |
8 |
1.14 |
2.03 |
22.59 |
885 |
75 |
4 |
8 |
1.14 |
2.03 |
24.13 |
1177 |
95 |
3 |
6 |
1.14 |
2.03 |
26.29 |
1523 |
110 |
2 |
6 |
1.14 |
2.03 |
27.76 |
1751 |
130 |
1 |
6 |
1.40 |
2.03 |
30.96 |
2187 |
150 |
1/0 |
6 |
1.40 |
2.03 |
33.27 |
2637 |
170 |
2/0 |
6 |
1.40 |
2.03 |
36.00 |
3200 |
195 |
3/0 |
4 |
1.40 |
2.03 |
39.01 |
3969 |
225 |
4/0 |
4 |
1.40 |
2.03 |
42.09 |
4827 |
260 |
250 |
4 |
1.65 |
2.79 |
47.78 |
5845 |
290 |
300 |
3 |
1.65 |
2.79 |
51.10 |
6903 |
320 |
350 |
3 |
1.65 |
2.79 |
53.82 |
7887 |
350 |
400 |
3 |
1.65 |
2.79 |
56.69 |
8933 |
380 |
500 |
2 |
1.65 |
2.79 |
61.62 |
10998 |
430 |